Tuesday, 27 September 2011

INTRODUCTION TO EARTHING SYSTEM DESIGN

EARTHING SYSTEM DESIGN 
Earthing is connection to earth to provide absolute zero potential. Earthing is given to the body of equipment so as to divert fault current to ground through neutral wire. operator remains safe, since current gets lower impedance path.
Purpose of earthing is to provide a low potential path to fault current which result in tripping the protective device & thus cut off the supply. Once the supply is cut off, both equipment & operator is safe. But remember earthing without the use of protective device in the circuit is of no use.
the term earthing means connection of neutral to the earth(ground).when any fault is occured then the fault current is given to earth to expose it . It is necessary to protection of operator. earthing is done by a bare simple conductor
 Earthing is connecting the neutral of the electrical
Equipment to the ground.

EARTHING AND BOND
Bonding is connecting wires together so they act as a single wire and all points along the wire have the same voltage/potential.

It all depends on the supply Normally in a domestic situation you have a combined neutral earth supply Typically you will require a 16mm main earth from the incoming mains to the consumer unit .Then a 10mm main bonding conductor from the consumer unit to the water pipe within 600 mm of the stop tap where it enters the property as well as the gas services again within 600mm I both these are located together then you can use the same wire as long as it is unbroken between clamps .In addition the pipes need to be bonded together with 6mm earth cable ie hot ,cold,gas and heating this is normally done in an airing cupboard or behind the heating unit.There are circumstances when additional bonding is required such as a room containing a bath or shower where all exposed pipework must be bonded together locally. hope it helps
These have been designated in the IEE Regulations using the letters: T, N, C and  S. These letters stand for:
 T    -  terre  (French for earth) and meaning a direct connection to earth. 
N    -  neutral
C    -  combined
S    -  separate.

When these letters are grouped, they form the classification of a type of system. 
The first letter denotes how the supply source is earthed.  
The second denotes how the metalwork of an installation is earthed.   The third and fourth indicate the functions of neutral and protective conductors.
 TT SYSTEM
 A TT system has a direct connection to the supply source to earth and a direct connection of the installation metalwork to earth.  An example is an overhead line supply with earth electrodes, and the mass of earth as a return path as
TN-S SYSTEM
 A TN-S system has the supply source directly connected to earth, the installation metalwork connected to the neutral of the supply source via the lead sheath of the supply cable, and the neutral and protective conductors throughout the whole system performing separate functions.
The resistance around the loop P-B-N-E should be no more than 0.8 ohms.
 TN-C-S SYSTEM
A TN-C-S system is as the TN-S but the supply cable sheath is also the neutral, i.e. it forms a combined earth/neutral conductor known as a PEN (protective earthed neutral) conductor.  
The installation earth and neutral are separate conductors.
This system is also known as PME (protective multiple earthing).
The resistance around the P-B-N-N loop should be less than 0.35 ohms.
SUMMARY OF EARTHING SYSTEMS
 The TT method is used mostly in country areas with overhead transmission lines. In contrast to the TN-S system there is no metallic path from the consumer's terminals back to the sub-station transformer secondary windings.  Because the earth path may be of high resistance, a residual current circuit-breaker (R.C.C.B.) is often fitted so that if a fault current flows in the earth path then a trip disconnects the phase supply.  
For protection against indirect contact in domestic premises, every socket outlet requires an RCCB with a maximum rated current of 30mA.
The TN-S system of wiring uses the incoming cable sheath as the earth return path and the phase and neutral have separate conductors.  The neutral is then connected to earth back at the transformer sub-station.
Remember in TN-S, the T stands for earth (terre), N for neutral and S denotes that the protective (earth) and neutral conductors are separate.
 The TN-C-S system has only two conductors in the incoming cable, one phase and the other neutral.  The earth is linked to the neutral at the consumer unit.  The neutral therefore is really a combined earth/neutral conductor hence the name PME.
 In order to avoid the risk of serious electric shock, it is important to provide a path for earth leakage currents to operate the circuit protection, and to endeavour to maintain all metalwork at the same potential.  This is achieved by bonding together all metalwork of electrical and non-electrical systems to earth.
The path for leakage currents would then be via the earth itself in TT systems or by a metallic return path in TN-S or TN-C-S systems.

1 comment:

  1. Very nice information about earthing. We are manufacturing units and almost every segment of industrial sphere. Assurance against successful attempt of security towards hazardous fault current, surges or any utility switching and follow-up is primarily the deal of earthing system. Copper Clad steel conductor, Lightning protection system, Surge protection devices are the installations when inculcated in parallel, finds susceptibility for every possible tragic action due to excessive amount of current and transient over-voltages.

    ReplyDelete